When there is no commercial power and the PV power is insufficient, the energy storage station shall be used; if the energy storage station is insufficient, the power generation shall be used; if the PV power is sufficient, the energy storage shall be charged. The minimum load of the unit shall be ensured when generating power. Setting mode: island mode Setting priority: PV > energy storage > power generation When the energy storage power station is started (VF), PV is switched on to generate power, and PV power is controlled to ensure that the energy storage station does not reverse power; When the power or rotating reserve of the energy storage station is insufficient, the generator set starts (VF), and the energy storage station changes to PQ mode; When the capacity of the energy storage station is insufficient, the generator set starts (VF), the energy storage station stops and exits the power supply sequence; When the energy storage station exits the power supply sequence, if the PV power is sufficient, the energy storage station will be charged until the charging reaches the required capacity, and then it will enter the power supply sequence again, and the energy storage station will start up (PQ); When the power station is sufficient, the VF unit will be transferred to reserve mode when the power station is shut down. |